KNX switch actuator, 1-gang
Description
Intended use
- Switching of electrical loads via relay contact
- Reading in switching states of installation switches or push-buttons and other floating contacts at inputs 1...3
- Signal evaluation of condensation (ref.-no.: BTS 01) and leakage sensors (ref.-no.: LES 01) at inputs 1...3
- Acquisition of temperature values via NTC temperature sensor at input 3 (ref.-no.: FF 7.8)
- Installation in flush box according to EN 60670-1
Product characteristics
- Output can be operated via KNX telegrams or extension inputs
- Three extension inputs for connecting floating contacts or dew/leakage sensors. NTC temperature sensor can be connected to input 3.
- Supply via bus, no additional power supply necessary
- KNX Data Secure compatible
- Can be updated with the ETS Service App
Characteristics switching operation
- Operation as NO or NC contacts
- Feedback function
- Logic operation and forcing function
- Central switching function
- Time functions: switch-on delay, switch-off delay, staircase lighting timer with pre-warning function
- Scene function
- Operating hours counter
- Operating functions switching, dimming (including colour temperature), controlling blinds, value transmitter (1 byte, 2 byte, 3 byte and 6 byte incl. RGBW und colour temperature presets), scene extension etc.
- Disabling function
- Debounce time adjustable
- Logic gates
- Transformer (conversion)
- Disabling element
- Comparator
- Limit value switch
Technical Details
Specification
Ambient temperature: −5 ... +45 °C
Storage/transport temperature: −25 ... +70 °C
Dimensions (W x H x D): 48 x 50 x 28 mm
KNX medium: TP 256
Commissioning mode: S-mode
Rated voltage KNX: DC 21 ... 32 V SELV
Current consumption KNX: 5 ... 18 mA
Connection, KNX: terminal connected to control cable
Outputs
Connection mode: screw terminals
Switching voltage: AC 250 V ~
Switching current: 16 A
Fluorescent lamps: 16 AX
Switch-on current 200 µs: max. 800 A
Switch-on current 20 ms: max. 165 A
Connected load
Ohmic load: 3000 W
Capacitive load: max. 16 A (140 µF)
Motors: 1380 VA
Incandescent lamps: 3000 W
HV halogen lamps: 2500 W
HV LED lamps: max. 400 W
LV halogen lamps with
electronic transformers: 1500 W
inductive transformers: 1200 VA
Compact fluorescent lamps
non-compensated: 1000 W
parallel compensated: 1160 W / 140 µF
Reduction of switching current
for every 5 °C exceededing 35 °C: −10 %
for installation into wooden or hollow walls: −15 %
for installation into multiple combinations: −20 %
Connection
Connection mode: screw terminals
single wire: 1 x 0.5 ... 4 mm²
stranded without ferrule: 1 x 0.5 ... 4 mm²
stranded with ferrule: 1 x 0.5 ... 2.5 mm²
Inputs
Control cable: YY6x0.6 (preterminated)
Input type: floating contact
Number: 3
Total length of extension unit cable: max. 10 m
Cable type: J-Y(St)Y
Voltage satellite inputs: approx. 5 V
Properties
Properties
Technology | KNX |
Brand | JUNG |