KNX heating actuator, 6-gang with controller
Description
Intended use
- Switching of electrothermal actuators for heaters or cooling ceilings
- Installation in distribution boxes on DIN rail according to EN 60715
Product characteristics
- Integrated room temperature control with setpoint value specification
- Six independent controllers to control up to six independent rooms
- Controller function for heating and cooling
- Switching operation or PWM operation
- Actuators with characteristics opened or closed without power controllable
- Valve drives for 230 V or 24 V controllable
- Outputs can be operated manually, construction site mode
- Feedback in manual mode and in bus mode
- Disabling of individual outputs manually or via bus
- Overload-protected, short circuit-protected; error indication with LED
- Protection against jamming valves
- Forced position
- Various setpoints for forced position or emergency operation in case of bus failure for summer or winter
- Cyclical monitoring of the input signals can be parameterised
- Feedback via bus, e.g. in case of mains failure, overload or sensor failure
Technical Details
Specification
Rated voltage: AC 110 ... 230 V ~, 50/60 Hz
Stand-by power: max. 0.4 W
Power loss: max. 1 W
KNX medium: TP 256
Rated voltage KNX: DC 21 ... 32 V SELV
Power consumption KNX: max. 250 mW
Ambient temperature: −5 ... +45 °C
Storage/transport temperature: −25 ... +70 °C
Heating outputs
Contact type: semiconductor (triac), ε
Switching voltage: AC 24 / 230 V ~
Mains frequency: 50/60 Hz
Switching current: 5 ... 160 mA
Switch-on current: max. 1.5 A (2 s)
Switch-on current: max. 0.3 A (2 min)
Number of drives per output
230 V drives: max. 4
24 V drives: max. 2
Mounting width: 72 mm (4 rail units)
Connection, outputs
Connection mode: screw terminals
single wire: 1 x 0.5 ... 4 mm²
stranded without ferrule: 1 x 0.5 ... 4 mm²
stranded with ferrule: 1 x 0.5 ... 2.5 mm²
Properties
Properties
Technology | KNX |
Brand | JUNG |
Mounting | DIN Rail |
Outputs | 6 |