***Important Dates: Orders for non-stock items 2nd December | Last orders for pre-Christmas Delivery 20th December | Shipping resumes 2nd January***

Battery Module, 12 V DC, MDRC
ABB AM/S12.1

Battery Module, 12 V DC, MDRC

Product code: GHQ6310062R0111
Battery module for maintaining bus voltage during power failure. To be used with Uninterruptible EIB Power Supply SU/S 30.640.1
Price (Excluding VAT)
£215.68

Description

Sealed lead acid battery module for maintaining the ABB i-bus system voltage (for up to a minimum of 10 minutes) in case of a mains failure in connection with the Uninterruptible EIB Power Supply SU/S 30.640.1. Connection is made via standard cables.

The Battery Module is for DIN rail mounting device and can easily be snapped onto the mounting rail beneath the Uninterruptible EIB Power Supply.

The back-up time is dependent on the bus load, however, a minimum of 10 minutes is guaranteed when the EIB line is at capacity (64 bus devices).

With integrated PTC temperature sensor for monitoring the charging voltage and integrated fuse.

The temperature sensor must always be connected to ensure that the battery is charged correctly!

Technical Details

Specification

  • Sealed lead acid battery
  • Requires uninterruptible KNX power supply SU/S 30.640.1.
  • Nominal Voltage: 12VDC
  • Battery Capacity: 1 Ah
  • Charging Current: 150mA
  • Charging Time: Max 10h
  • Mains Failure Back-up time: Min. 10 Minutes (Dependent on bus load; the back up time can be reduced due to ageing of the battery module.
  • Integrated Temperature Sensor
  • Fuse: Self Healing
  • Operation Temperature: +5 °C ... +45 °C
  • Storage Temperature: -25 °C ... +20 °C


Properties

Properties

Technology KNX
Brand ABB
Mounting DIN Rail
Operating voltage 12VDC
IP rating IP20
Mounting Width 8MW
EAN 40 16779 51481