Energy Actuator, 3-fold, 16/20 AX, MDRC
ABB SE/S3.16.1

Energy Actuator, 3-fold, 16/20 AX, MDRC

Product code: 2CDG110136R0011
Measures energy consumption on each of 3 Relays. Various electrical values (Active Power, Current, Voltage, Frequency) can be monitored and peak loads can be limited through a simple load control.
Price (Excluding VAT)
£568.47

Description

The Energy Actuator is a modular iinstallation device in Pro M design for installation in the distribution board. The device is especially suitable for switching loads with high peak inrush currents such as lighting equipment with compensation capacitors or fluorescent lamp loads (AX) to EN 60 669.

Manual operation is possible using a keypad on the device. This simultaneously indicates the switching state. The Energy Actuator can switch up to 3 independent electrical loads via floating contacts. The maximum load current per output is 20 A.

The connection of the outputs is implemented using universal head screw terminals. Each output is controlled separately via the KNX.

Individual outputs can be copied or exchanged to reduce the programming effort.

The parameterisation is undertaken via the ETS. The connection to the KNX is implemented using the bus connection.

The following functions can be set:

  • Recording of the active consumption in watt hours (Wh) with a main meter and a flexibly programmable intermediate meter for each output. The intermediate meter can be started and stopped in dependence on defined events (1 bit telegrams, time, and consumption). Warnings can be sent on the KNX depending on these events.
  • Current, voltage, active power and frequency can be recorded and monitored with the aid of threshold values. Warnings can be sent on the  KNX depending on these events. Recording of apparent power, power factor and crest factor are also available.
  • A simple load control can be implemented. Every Energy Module can be configured as a Server, and the total power of a system by up to ten further Energy Actuators can be recorded. Load shedding stages are sent on the bus, and the devices are shutdown according to their own programmable load shedding stage.
  • Function Time: Staircase lighting, switch ON and OFF delay and flashing  
  • Recall 8 bit scenes
  • Logical functions AND, OR, XOR and GATE
  • Functions forced operation and safety 
  • Selection of the default position at bus voltage failure and bus voltage recovery

Technical Details

Specification

  • Bus Voltage: KNX Bus 21...32VDC
  • Bus Current Consumption: Max 12mA
  • Outputs: 3

    • Rated Voltage: 250/440 V AC (50/60 Hz)
    • Rated Current: 16/20Ax,C-Load


Measuring Range

  • Active consumption/active power: 5.7W...4,600W
  • Current (AC): 0.025...20 A
  • Voltage (AC): 95...265V
  • Frequency: 45...65HZ

Properties

Properties

Technology KNX
Brand ABB
Mounting DIN Rail
Operating voltage KNX Bus (29VDC)
Outputs 3
IP rating IP20
Mounting Width 4MW
EAN 40 16779 70977
Ivory Egg uses cookies to make your experience better and provide necessary site functionality. By using our website, you agree to set the cookies and accept the privacy policy