ClimaEco Boiler/Chiller Interface, 1 fold
Description
Used as an interface between the KNX system and a heat generator or chiller. Via an analog output (010V) the set point or set point adjustment temperature can be transmitted to the heat generator/chiller. The set point itself is received via KNX. Via two binary inputs the device can monitor the status of the heat generator/chiller (via potential free contacts) and send it on the KNX bus. A relay output (5A) is included to switch or enable/disable the heat generator/chiller. With an additional relay output (5A) the pump of the heat generator/chiller can be switched on and off. Via 3 binary inputs it is possible to monitor the status of the pump (via potential free contacts) and integrate these feedbacks into the control of the pump.
The device supports the ABB i-bus Tool for advanced diagnosis and improved commissioning.
Technical Details
Specification
- Supply voltage: KNX 29VDC <12mA
- Interface Outputs: 1
- Voltage: 0...10 V DC
- Pump Outputs: 2
- Rated Voltage: 250VAC
- Rated Current Per Output Pair: 5A
- Inputs for Temp 2
- Inputs for contact Scanning: 5 (1 mA 12 V)
- Degree of protection: IP 20 acc. EN 60529
- Din Rail Mounting
Properties
Properties
Technology | KNX |
Brand | ABB |
Mounting | DIN Rail |
Inputs | 7 |
Operating voltage | KNX Bus (29VDC) |
Outputs | 1 |
Output Type | Analogue 0-10V |
HVAC support | None |
IP rating | IP20 |
Mounting Width | 6MW |