FanCoilCtrl,3x0-10V
Description
For the control of fan coil units. Via two analog outputs, two analog valves or one 6-way valve drive can be controlled for heating and cooling. For the fan control the devices features a 0...10V analog output. A relay output switches an additional load of up to 10 A, such as auxiliary heating. Over 4 inputs the room status can be detected and monitored (Use for window contact, dew point sensor, level sensor or temperature sensor). Also it is possible to connect one analog room control unit (SAR/A or SAF/A) to the inputs of the device. The device has an integrated room temperature controller for the control of the room temperature, which can be used directly to control the outputs of the device.
The device supports the ABB i-bus Tool for advanced diagnosis and improved commissioning.
Technical Details
Specification
- Supply voltage: KNX 29VDC <12mA
- Valve Outputs: 3
- Rated Voltage: 0...10V
- Output Current Per Rated Pair: 0.5A
- Fan Speed Outputs : 1
- Rated Voltage: 0...10V
- Auxillary Outputs: 1
- Rated Voltage: 250VAC
- Rated Current : 16A
- Inputs for Temp: 4
- Degree of protection: IP 20 acc. EN 60529
- Din Rail Mounting
Properties
Properties
Technology | KNX |
Brand | ABB |
Mounting | DIN Rail |
Inputs | 4 |
Operating voltage | KNX Bus (29VDC) |
Outputs | 4 |
HVAC support | Temperature Sensing + Regulation |
IP rating | IP20 |
Mounting Width | 6MW |