GIRA
212300
Area or Line coupler for KNX
Product code:
2123 00
Provides a data link between two KNX lines/segments/areas and ensures galvanic isolation between these lines/segments/areas.
Description
- Can be operated as an area coupler, line coupler, segment coupler or amplifier by addressing.
- Use as a segment coupler to extend a line with additional line segments, with a filter table configurable for the line segment.
- Filter functions for group telegrams and physically addressed telegrams can be configured separately in the ETS.
- Manual operation to deactivate the filter functions (separately for group telegrams and physically addressed telegrams).
- Indication of the current operating mode and status of the filter functions via multi-coloured status LEDs.
- Filtering, forwarding and blocking of encrypted and unencrypted telegrams regardless of start-up as a KNX Data Secure product.
- Secure proxy for connecting an unencrypted and encrypted line (e.g. in use between a building (unencrypted line) and the outside (encrypted line)) or when using two devices to create a secure bridge between two unencrypted lines.
- Automatic setting of the functionality as a secure proxy in ETS6 after secure start-up using a device certificate.
- Configuration and start-up of the device from ETS 5 from version 5.7.7 when used as an area coupler, line coupler, or amplifier. With ETS 6 from version 6.1.0 (recommended), additional use as a segment coupler or secure proxy
Technical Details
Specification
KNX medium: TP256
Rated voltage KNX: DC 21 to 32 V SELV
KNX current consumption
higher-level line: 9 mA
lower-level line: 5 mA
Connections
KNX: Connection and junction terminal
Ambient temperature: -5 °C to +45 °C
Properties
Properties
Technology | KNX |
Brand | GIRA |
Mounting | DIN Rail |
Operating voltage | KNX Bus (29VDC) |
IP rating | IP20 |
Mounting Width | 1MW |
KNX Secure | Yes |