GIRA
222400
KNX control unit 1-10 V, 4-gang with manual mode
Product code:
2224 00
Designed with flexibility in mind the Gira 1-10v control unit has 4 control outputs and 4 relay outputs which can can be configured in 5 different formats. Unused relays can be controlled independently or control outputs can be grouped to a single relay for RGB control. There are a wide range of additional features including logo,scenes, sequences, burn in timers and time functions.
Description
Features
- The controller unit switches and dims electrical devices that have a 1-10 V interface.
- Five device configurations can be selected. This leads to the assignment of four individually-controllable dimming channels to the switching outputs (e.g. four dimming channels are assigned to one switching relay to control a RGBW light).
- Relay outputs that are not associated with a dimming channel can be used as freely-acting switching actuator channel.
- Reactions in case of bus voltage failure and restoration can be set following an ETS programming process.
- Manual actution of outputs independent of the bus with mechanical switching position indication.
- Delay for actively transmitted feedback messages following bus voltage recovery.
- Logical linking function configurable per channel.
- Up to three central switching functions for the joint control of all dimming and switching channels.
- Switch-on times of the relay outputs can be recorded and evaluated by the elapsed operating time meter.
- Group feedback of all switching conditions possible.
Dimming channels
- Four individually-controllable dimming channels.
- Feedback on switching condition and brightness value.
- Dimmable brightness range can be set.
- Dimming behaviour and dimming characteristics can be parameterised.
- Soft switch-on and soft switch-off function.
- Block function or forced setting function can be parameterised.
- Time functions (switch-on delay, switch-off delay, staircase light function). With the staircase light function, the reaction at the end of the switch-on time can be configured.
- Inclusion of a dimming channel in up to ten scenes is possible.
- The burning-in function allows for the start-up of new fluorescent lamps prescribed by lighting manufacturers.
Switching actuator operation (optional)
- Independent switching of switch outputs A2 to A4.
- NO contact or NC contact operation.
- Feedback from the switching condition.
- Block function or forced setting function can be parameterised.
- Time functions (switch-on, switch-off delay, staircase light function - also with advance warning function).
- Can be integrated in the light scenes. Up to ten internal scenes per switching output are programmable.
- Cyclical monitoring of incoming switching telegram is configurable.
Technical Details
Specification
Bus Connection
- Bus Voltage: KNX Bus 21...32VDC
- Bus Current Consumption: 6mA
Relay
- Number: 4
- Contact: 1 x zero-voltage NO contact each, flip-flop
Control outputs
- Control voltage: 1 to 10 V
- Control current per output: max. 100 mA
- Cable length: max. 500 m at 0.5 mm²
Switching outputs
- Switching voltage: AC 250/400 V
- Switching current 230 V AC1: 16 A
- Switching current 230 V AC3: 10 A
- Switching current 400 V AC1: 10 A
- Switching current 400 V AC3: 6 A
- Fluorescent lamps: 16 AX
Lamp loads
- Light bulbs: 3680 W
- HV halogen lamps: 3680 W
- Wound transformer: 2000 VA
- Gira Tronic transformer: 2500 W
Fluorescent lamps T5/T8
- Uncompensated: 3680 W
- Parallel-compensated: 2500 W/200 µF
- Duo-circuit: 3680 W/200 µF
Compact fluorescent lamps
- Uncompensated: 3680 W
- Parallel-compensated: 2500 W/200 µF
Mercury-vapour lamps
- Uncompensated: 3680 W
- Parallel-compensated: 3680 W/200 µF
Properties
Properties
Technology | KNX |
Brand | GIRA |
Mounting | DIN Rail |
Operating voltage | KNX Bus (29VDC) |
Outputs | 4 |
IP rating | IP20 |
Mounting Width | 4MW |
EAN | 4010337018858 |