KNX switching actuator 1-gang 16 A with binary input, 3-gang
GIRA 506100

KNX switching actuator 1-gang 16 A with binary input, 3-gang

Product code: 506100
Price (Excluding VAT)
£99.00

Description

Depending on the ETS parameterisation in the application for switches, buttons or contacts, inputs 1 and 2 either act internally on the relay output or separately on the KNX. Input 3 always acts on the KNX.

Functions for the inputs when acting on the KNX (switching, dimming, blind, value transmitter, scene auxiliary unit, 2-channel operation, controller auxiliary unit, no function).

Switching: Command for closing and opening of the contact adjustable (no reaction, ON, OFF, TOGGLE).

Dimming: Dimming of brightness and/or colour temperature. Command for closing the contact, time between switching and dimming, dimming in different steps, telegram repetition in case of long signal at the input, and sending of a stop telegram at the end of the dimming process all configurable.

Blinds: Command for closing the contact and the operating concept can be parameterised. Times for short and long signal at input and slat adjustment are adjustable.

Value transmitter: Functionality as 1-byte, 2-byte, 3-byte or 6-byte value transmitter including colour temperature and colour value transmitter possible. Individually configurable values. Value adjustment is optionally possible with a long signal at the input (not with the 6-byte value transmitter).

Scene auxiliary unit: Mode of operation (with or without memory function) and the scene number are adjustable.

2-channel operation: When the contact at the input closes, up to two telegrams can be sent out on the KNX. Operating concept adjustable (only channel 1 or channel 2/both channels). The mode of operation of the channels (1-bit, 1-byte, 2-byte, 3-byte, 6-byte) can be configured separately.

Controller auxiliary unit: Mode of operation (operating mode switching, forced operating mode switching, presence function and target value adjustment) configurable.

Disabling of all or individual inputs via a 1-bit object possible. Polarity of the blocking object, behaviour at the beginning and end of blocking, and behaviour during an active blocking can be adjusted.


Logic functions

  • The device has 8 internal logic functions.
  • Logic gate (AND, OR, exclusive AND, exclusive OR, each with up to 4 inputs).
  • 1-bit to 1-byte converter with input filter, blocking object and specification of output values.
  • Blocking element with filter and time functions and blocking object.
  • Comparator for values with 9 different input data formats and many comparison operations.
  • Limit value switch with hysteresis with upper and lower threshold values for 9 different input data formats. Including specification of the 1-bit output values.
  • The logic functions have their own KNX communication objects and can process telegrams from the actuator or other bus devices.
  • Switching electrical consumers via a relay contact.
  • Device has three inputs with a common reference potential.
  • Reading in switching states of installation switches or push buttons and other zero-voltage contacts at inputs 1 to 3.
  • Signal analysis of dew and leakage sensors (see accessories) at inputs 1 to 3.
  • Recording of temperature values via remote sensors (see accessories) at input 3.
  • Up to 8 independent logic functions for implementing simple or complex logical operations.
  • Actively transmitting feedback or status messages can be delayed after a bus voltage recovery or ETS programming mode.
  • Bistable relay.

Switching functions

  • NO contact or NC contact operation.
  • Central switching function via up to 6 switch objects (ON, OFF, permanently ON, permanently OFF).
  • Feedback on switching: Active or passive feedback function.
  • Reaction in case of bus voltage failure or bus voltage recovery can be set following an ETS programming process.
  • Logical linking function.
  • Block function or forced setting function can be parameterised.
  • Extended blocking function with acknowledgement option.
  • Time functions (switch-on and switch-off delay, staircase light function – also with advance warning function).
  • Can be integrated in the light scenes: Up to 64 internal scenes can be parameterised.
  • Scene memory function: Additional visual feedback.
  • Extended scene retrieval (toggling of scenes).
  • Elapsed operating time meter can be activated.
  • Input monitoring for cyclic updating of the switching object with safety position.


Technical Details

Specification

KNX medium: TP256

Connections
KNX:Connection terminals to control line
Inputs:Connection terminals to control line
Load:Screw terminals

Connections: Max. 4 mm²

Inputs: 3

Input type: Zero-voltage

Polling voltage
Auxiliary inputs: approx. 5 V

Total length
Auxiliary input cable: max. 10 m

Ambient temperature: -5 °C to +45 °C

Rated voltage: 

KNX: DC 21 to 32 V SELV

Switching Capacity: AC 205 V, 16AX

Maximum switch-on current: 800 A (200 µs), 165 A (20 ms)

Connected load

  • Ohmic load: 2500 W
  • Capacitive load: 16 A, max. 140 µF
  • Motors (blind or fan): 1380 W
  • Light bulbs: 2300 W
  • HV halogen lamps: 2300 W
  • HV LED lamps: typically 400 W
  • Wound transformer: 1200 VA
  • Tronic transformer: 1500 W
  • Fluorescent lamps, uncompensated: 1000 VA
  • Fluorescent lamps, duo-circuit: 2300 VA
  • Fluorescent lamps, parallel-compensated: 1160 VA


Properties

Properties

Technology KNX
Brand GIRA
Inputs 3

Documents & Downloads