KNX switching actuator 1-gang 16 A with binary input, 3-gang
Description
Depending on the ETS parameterisation in the application for switches, buttons or contacts, inputs 1 and 2 either act internally on the relay output or separately on the KNX. Input 3 always acts on the KNX.
Functions for the inputs when acting on the KNX (switching, dimming, blind, value transmitter, scene auxiliary unit, 2-channel operation, controller auxiliary unit, no function).
Switching: Command for closing and opening of the contact adjustable (no reaction, ON, OFF, TOGGLE).
Dimming: Dimming of brightness and/or colour temperature. Command for closing the contact, time between switching and dimming, dimming in different steps, telegram repetition in case of long signal at the input, and sending of a stop telegram at the end of the dimming process all configurable.
Blinds: Command for closing the contact and the operating concept can be parameterised. Times for short and long signal at input and slat adjustment are adjustable.
Value transmitter: Functionality as 1-byte, 2-byte, 3-byte or 6-byte value transmitter including colour temperature and colour value transmitter possible. Individually configurable values. Value adjustment is optionally possible with a long signal at the input (not with the 6-byte value transmitter).
Scene auxiliary unit: Mode of operation (with or without memory function) and the scene number are adjustable.
2-channel operation: When the contact at the input closes, up to two telegrams can be sent out on the KNX. Operating concept adjustable (only channel 1 or channel 2/both channels). The mode of operation of the channels (1-bit, 1-byte, 2-byte, 3-byte, 6-byte) can be configured separately.
Controller auxiliary unit: Mode of operation (operating mode switching, forced operating mode switching, presence function and target value adjustment) configurable.
Disabling of all or individual inputs via a 1-bit object possible. Polarity of the blocking object, behaviour at the beginning and end of blocking, and behaviour during an active blocking can be adjusted.
Logic functions
- The device has 8 internal logic functions.
- Logic gate (AND, OR, exclusive AND, exclusive OR, each with up to 4 inputs).
- 1-bit to 1-byte converter with input filter, blocking object and specification of output values.
- Blocking element with filter and time functions and blocking object.
- Comparator for values with 9 different input data formats and many comparison operations.
- Limit value switch with hysteresis with upper and lower threshold values for 9 different input data formats. Including specification of the 1-bit output values.
- The logic functions have their own KNX communication objects and can process telegrams from the actuator or other bus devices.
- Switching electrical consumers via a relay contact.
- Device has three inputs with a common reference potential.
- Reading in switching states of installation switches or push buttons and other zero-voltage contacts at inputs 1 to 3.
- Signal analysis of dew and leakage sensors (see accessories) at inputs 1 to 3.
- Recording of temperature values via remote sensors (see accessories) at input 3.
- Up to 8 independent logic functions for implementing simple or complex logical operations.
- Actively transmitting feedback or status messages can be delayed after a bus voltage recovery or ETS programming mode.
- Bistable relay.
Switching functions
- NO contact or NC contact operation.
- Central switching function via up to 6 switch objects (ON, OFF, permanently ON, permanently OFF).
- Feedback on switching: Active or passive feedback function.
- Reaction in case of bus voltage failure or bus voltage recovery can be set following an ETS programming process.
- Logical linking function.
- Block function or forced setting function can be parameterised.
- Extended blocking function with acknowledgement option.
- Time functions (switch-on and switch-off delay, staircase light function – also with advance warning function).
- Can be integrated in the light scenes: Up to 64 internal scenes can be parameterised.
- Scene memory function: Additional visual feedback.
- Extended scene retrieval (toggling of scenes).
- Elapsed operating time meter can be activated.
- Input monitoring for cyclic updating of the switching object with safety position.
Technical Details
Specification
KNX medium: TP256
Connections
KNX:Connection terminals to control line
Inputs:Connection terminals to control line
Load:Screw terminals
Connections: Max. 4 mm²
Inputs: 3
Input type: Zero-voltage
Polling voltage
Auxiliary inputs: approx. 5 V
Total length
Auxiliary input cable: max. 10 m
Ambient temperature: -5 °C to +45 °C
Rated voltage:
KNX: DC 21 to 32 V SELV
Switching Capacity: AC 205 V, 16AX
Maximum switch-on current: 800 A (200 µs), 165 A (20 ms)
Connected load
- Ohmic load: 2500 W
- Capacitive load: 16 A, max. 140 µF
- Motors (blind or fan): 1380 W
- Light bulbs: 2300 W
- HV halogen lamps: 2300 W
- HV LED lamps: typically 400 W
- Wound transformer: 1200 VA
- Tronic transformer: 1500 W
- Fluorescent lamps, uncompensated: 1000 VA
- Fluorescent lamps, duo-circuit: 2300 VA
- Fluorescent lamps, parallel-compensated: 1160 VA
Properties
Properties
Technology | KNX |
Brand | GIRA |
Inputs | 3 |