Modbus RTU to Modbus TCP Router - 32 devices
Description
FEATURES
- UL Certified
- Support for up to 5 simultaneous Modbus TCP Clients
- Support for up to 32 full-load RTU devices
- Modbus diagnose signals available in both MAPS and as Modbus registers
- Easy integration & updates with Intesis MAPS
This bidirectional gateway provides a straightforward and fast integration thanks to its unique onboard features.
Thanks to its support for both Modbus RTU and TCP, with the possibility to work together at the same time, a seamless integration with any Modbus BMS or controller it is guaranteed.
The configuration is carried out using the Intesis MAPS software. This one allows you to define your own settings for the device. Also, it will be able to download all the available project templates or to import any created/exported project template on your computer.
Technical Details
Specification
Enclosure
- Plastic, type PC (UL 94 V-0)
- Net dimensions (dxwxh): 93x53x58 mm
- Recommended space for installation (dxwxh): 100x60x70mm
- Colour: Light Grey. RAL 7035
Mounting
- Wall.
- DIN rail EN60715 TH35.
Terminal Wiring (for power supply and low-voltage signals)
- Per terminal: solid wires or stranded wires (twisted or with ferrule)
- 1 core: 0.5mm2... 2.5mm2
- 2 cores: 0.5mm2... 1.5mm2
- 3 cores: not permitted
Power
- 1 x Plug-in screw terminal block (3 poles)
- Positive, Negative, Earth
- 24VDC +/-10% / 6.5W
Ethernet
- 1 x Ethernet 10/100 Mbps RJ45
- 2 x Ethernet LED: port link and activity
Port
- 1 xSerial EIA485 (Plug-in screw terminal block 3 poles) A, B, SGND (Reference ground or shield)
- 1500VDC isolation from other ports
Operation Temperature
- 0¡C to +60¡C
Operational Humidity
- 5 to 95%, no condensation
Protection
- IP20 (IEC60529)
Properties
Properties
Technology | KNX |
Brand | INTESIS |
Mounting | DIN Rail |
Operating voltage | 24VDC |
IP rating | IP20 |
Mounting Width | 4MW |