Last Dates for shipments: Palletways 22nd December for next day pallets / 19th December for economy pallets (UK) Scotland 12th December / NI 15th December

Royal Mail last day for shipping 19th December for Tracked 24. DPD Last day for shipping 22nd December for guaranteed next day delivery.

We will be closed from Christmas Day until the 5th of January.

KNX multistation controller
JUNG 23066REGHE

KNX multistation controller

Product code: 23066REGHE
Mutli input/ouput controller for small installations, hotel rooms or apartments.
Price (Excluding VAT)
£259.69

Description

Intended use

  • Switching of electrical loads with floating contacts
  • Switching of electrically-driven blinds, shutters, awnings and similar hangings
  • Switching of electrothermal drives
  • Polling of conventional switching or push-button contacts, window contacts etc. in KNX systems, for reporting of states, meter levels, operation of loads, etc.
  • Polling of external temperature sensors for heating control
  • Logic functions to control building functions
  • Mounting on DIN rail according to EN 60715 in distribution boxes

Product characteristics

  • Actuator functions: switching, blinds, electrothermal drives
  • Actuator function can be switched in pairs
  • Integrated push-button interface with 6 inputs
  • 2 integrated room temperature controllers
  • 2 inputs for temperature sensors (ref.-no. FF 7.8)
  • Outputs can be operated manually, construction site mode
  • Feedback in manual mode and in bus mode
  • Scene function
  • Disabling of individual outputs manually or by bus

Switching function

  • Max. 6 switching outputs
  • Operation as NO or NC contacts
  • Logic operation and forcing function
  • Feedback function
  • Central switching function with collective feedback
  • Time functions: switch-on delay, switch-off delay, staircase lighting timer with pre-warning function

Blinds function

  • Max. 3 blinds outputs
  • Suitable for 230 V AC motors
  • Blind/shutter position directly controllable
  • Slat position directly controllable
  • Feedback of movement status, blind/shutter position and slat position
  • Forced position through higher-level controller
  • Safety function: 3 independent wind alarms, rain alarm, frost alarm
  • Sun protection function

Function of valve drives

  • Max. 2 outputs for electrothermal drives
  • Switching operation or PWM operation
  • Actuators with characteristics opened or closed without power controllable
  • Emergency operation in case of bus voltage failure for summer and winter
  • Protection against jamming valves
  • Forced position
  • Cyclical monitoring of the input signals can be parameterised

Heating controller

  • 2 internal controllers to control two independent rooms
  • Control for heating or cooling, optionally with additional level
  • On-off, PWM or PI control
  • Predefined heating types (hot water heating, fan coil unit ...) or individual parameters possible

Inputs

  • 6 inputs for push-buttons
  • Input functions: switching, dimming, blinds control, light scene extension unit, brightness or temperature value transmitter
  • 2 inputs for external temperature sensors

Logic functions

  • Up to 10 logic operations with up to 8 inputs each, e.g. for AND, OR and XOR operations
  • Conversion of data point types, e.g. from 1-bit to 8-bit
  • Comparative operations, e.g. <, >, _, _
  • Arithmetic functions, e.g. +, _, *, :

Technical Details

Specification

KNX medium: TP 256

Rated voltage KNX: DC 21 ... 32 V SELV

Current consumption KNX: max. 20 mA

Current consumption KNX: min. 4 mA

Connection, KNX: terminal

Power loss: max. 6 W

Ambient temperature: _5 ... +45 C

Storage/transport temperature: _25 ... +70 C

Relay outputs

  • Contact type: floating relay contacts (_ contact)
  • Switch type: NO contact
  • Switching voltage: AC 250 V ~
  • Min. switching current AC: 100 mA
  • Switching current AC1 (cos _ > 0.8): 16 A
  • Switching current AC3 (cos _ < 0.8): 6 A
  • Fluorescent lamps: 16 AX
  • Switch-on current 200 µs: max. 800 A
  • Switch-on current 20 ms: max. 165 A
  • Switching voltage DC: DC 12 ... 24 V
  • Switching current DC 24 V: 6 A

Connected load, 230 V

  • Ohmic load: 3000 W
  • Blind / Fan motors: 1380 VA

Lamp loads 230 V

  • Incandescent lamps: 3000 W
  • HV halogen lamps: 2500 W
  • HV LED lamps: max. 400 W
  • Electronic transformers: 1500 W
  • Inductive transformers: 1200 VA

Fluorescent lamps T5/T8

  • non-compensated: 1000 W
  • parallel compensated: 1160 W / 140 µF
  • lead-lag circuit: 2300 W / 140 µF

Compact fluorescent lamps

  • non-compensated: 1000 W
  • parallel compensated: 1160 W / 140 µF

Mercury vapour lamps

  • non-compensated: 1000 W
  • parallel compensated: 1160 W / 140 µF

Electrothermal valve drives

  • Cycle time: min. 15 min

Connection, load

  • Connection mode: screw terminals
  • single wire: 0.5 ... 4 mm_
  • stranded without ferrule: 0.5 ... 4 mm_
  • stranded with ferrule: 0.5 ... 2.5 mm_

Inputs

  • Rated voltage: DC 3.3 V SELV
  • Signal duration: min. 100 ms
  • NO contacts: max. 50
  • NC contacts: max. 50
  • Cable length: max. 30 m

For cable lengths > 3 m, use shielded cables.

Connection, inputs:

  • Connection mode: screw terminals
  • single wire: 0.08 ... 1.5 mm_
  • stranded without ferrule: 0.08 ... 1 mm_
  • stranded with ferrule: 0.14 ... 0.5 mm_

Mounting width: 72 mm (4 rail units)

Properties

Properties

Technology KNX
Brand JUNG
Mounting DIN Rail
Operating voltage KNX Bus (29VDC)
Mounting Width 4MW

Documents & Downloads

Ivory Egg uses cookies to make your experience better and provide necessary site functionality. By using our website, you agree to set the cookies and accept the privacy policy