KNX Presence detector mini standard, white
Description
Intended use:
- Requirement-oriented control of lighting, room thermostats and other electrical loads in interior rooms
- Clamp mounting in suspended ceilings
- Ceiling installation on fixed ceilings in appliance box according to DIN 49073 with flush mounting set (PMM-UP-SET-WW)
- Surface-mounted ceiling installation with surface mounting set (PMM-AP-SET-WW)
Product characteristics:
- Integrated bus coupling unit
- 3 PIR sensors
- Detection field 360°
- Integrated brightness sensor
- Deployed as presence detector, motion detector, or for alert operation
- Output functions: Switching, staircase function, switching with forced position, value transmitter, light scene extension, operating mode setting for room temperature controller
- Extension of the detection area by way of operating several devices as main unit or extension unit
- Adjuster for manual adjustment of sensitivity
- Status LED: Flashes during motion detection; depending on programming in normal operation or only during the walking test mode
Presence detector function:
- Detection of the smallest motions e.g. at a workplace for detecting the presence of persons
- Switch on: Motion detection and brightness threshold not reached
- Switch off: No motion in the detection field and shut-off delay elapsed or brightness threshold exceeded
Motion detector function:
- Motion detection for passageways in buildings
- Switch on: Motion detection and brightness threshold not reached
- Switch off: No motion in the detection field and shut-off delay elapsed or brightness threshold exceeded
- After reacting and switching on, the motion detection works independently of the brightness.
Signalling mode:
- Brightness-independent detection of motions in the detection field
- Switch on: After detection of an adjustable number of motions within the set monitoring period
- Switch off: No motion in the detection field and shut-off delay elapsed
Technical Details
Specification
KNX medium: TP 256
Rated voltage KNX: DC 21 ... 32 V SELV
Current consumption KNX: max. 10 mA
Connection bus: terminal
Protection class: III
Ambient temperature: −25 ... +55 °C
Storage/transport temperature: −25 ... +70 °C
Relative humidity: 10 ... 100 % (no condensation)
Protection level: IP 44
Ceiling cut-out (Ø x D): 44 x 35 mm
Dimensions (Ø x H): 53.5 x 38 mm (with design ring)
Max. thickness of the suspended ceiling: approx. 25 mm
Installation depth: min. 35 mm
Distance between concrete ceiling and suspended ceiling: min. 20 mm
Design ring Ø inside: 35.6 mm
Design ring Ø outside: 53.5 mm
Profile height design ring: 1.8 mm
Profile height lens: 5.5 mm
Motion detection
Detection angle: 360°
Range: Ø approx. 12 m (mounting height 3 m)
Brightness sensor
Measuring range: 10 ... 2,000 lx
Accuracy (≤ 80 lx): ± 10 lx
Accuracy (> 80 lx): ± 5 %
Properties
Properties
Technology | KNX |
Brand | JUNG |
Colour/Material | White |
Mounting | Flat |
Operating voltage | KNX Bus (29VDC) |