KNX Universal Room actuator 110-230 V
Description
Intended use
- Switching of electrical loads AC 110-230 V with floating contacts
- Switching of electrically operated blinds, shutters, awnings and similar curtains
- Heating outputs: electronic outputs for switching electro-thermal valve drives
- Manual output control, provisional operation
- Feedback in manual control mode and in bus operation
- Scene function
- Disabling of individual outputs by hand or via the bus
- NO contact and NC contact operation
- Logic operation and forcing function
- Feedback function
- Central switching function with group feedback
- Time functions: ON-delay, OFF-delay, staircase lighting timer with early-warning function
- Suitable for AC motors 110-230 V
- Direct control of blind/shutter position
- Direct control of slat position
- Checkback of running state, blind/shutter position and slat position
- Forced-control position from primary control
- Safety function: 3 independent wind alarms, rain alarm, frost alarm
- Sun protection function
- Switching or PWM operation
- Control of valve drives with working characteristics "normally open" or "normally closedñ
- Overload and short-circuit protection
- Emergency operation in the event of bus failure for summer and winter
- Protection against jamming valves
- Forced-control position
- Rail mounting device, 4 rail units
- With manual electronic operation and LED status indication
- Only with the ETS 3.0d version or later versions the full functionality will be available.
- ETS product family: Output
- Product type: Binary output
Product characteristics
Switching function
Blind/shutter function
Control of valve drives 230 V
Ordering Information
Technical Details
Specification
KNX supply: DC 21 ... 32 V SELV
Power consumption KNX: max. 150 mW
Power supply mains: AC 110 ... 230 V ~, 50/60 Hz
Power loss: max. 6 W
Ambient temperature: _5 ... +45 C
Storing temperature: _25 ... +70 C
Mounting width: 72 mm (4 rail units)
Connection, KNX: terminal
Connection, mains and outputs:
- Connection mode: screw terminals
- single wire: 0.5 ... 4 mm_
- stranded without ferrule: 0.5 ... 4 mm_
- stranded with ferrule: 0.5 ... 2.5 mm_
Heating outputs
Number: 2
Contact type: semiconductor, _
Switching voltage: AC 230/240 V ~
Switching current: 5 ... 50 mA
Switch-on current: max. 1.5 A (2 s)
Number of drives per output: max. 4
Relay outputs
Number: 4 (2 channels for operating blinds)
Contact type: floating NO contact (µ contact)
Switching voltage: AC 230/240 V ~
Breaking capacity AC1: 16 A
Breaking capacity AC3: 6 A
Breaking capacity fluorescent lamps: 16 AX
Switching capacities per output
Ohmic load: 3000 W
Capacitive load: 16 A / max. 140 µF
Motors: 1380 VA
Lamp loads
- Incandescent lamps: 3000 W
- HV halogen lamps: 2500 W
- LV halogen lamps with
- electronic transformers: 1500 W
- inductive transformers: 1200 VA
- Fluorescent lamps:
- non-compensated: 1000 W
- parallel compensated: 1160 W / max. 140 µF
- lead-lag circuit: 2300 W / max. 140 µF
Approvals: VDE
Properties
Properties
Technology | KNX |
Brand | JUNG |
Mounting | DIN Rail |
Operating voltage | 230VAC |
Mounting Width | 4MW |