eNet radio switch/push-button actuator, 8-gang / blinds actuator, 4-gang
Description
Intended use
- Switching of lighting
- Switching of single-phase fan motors
- Controlling electrically driven blinds, shutters and awnings
- Operation with suitable eNet radio transmitters
- Operation with power supply (ref.-no. NT 1220 REG VDC) and receiver module (ref.-no. FM FK 32 REG) or eNet server
- Installation in distribution boxes on DIN rail according to EN 60715
Product characteristics
- Operating mode switch for switch-over of switch actuator, push-button actuator, blind actuator, shutter actuator or configuration via eNet server
- Status feedback to radio transmitter
- Scene operation possible
- Outputs switchable with Prog button
- Status indication of the outputs via LED
Switching operation:
- Switch-on telegram: Device switches on
- Switch-off telegram: Device switches off
Push-button operation:
- Relay contact remains closed as long as ON or OFF telegrams are being received
- The maximum switch-on time is 60 seconds
Operating mode "Venetian blind/Rolling shutter":
- Positioning of the blind and slats via scene recall
- Position for sun protection and twilight can be saved
- Blind/shutter running time can be saved
- Slat change-over time can be saved
- Fabric-stretching for awnings
Can be set with eNet server in switching/push-button operation:
- Operating mode for each output can be set separately
- Flash function
- Run-on time
- Switch-on delay / switch-off delay
- Operation as NO or NC contacts
- Switch-off warning
- Minimum switching repeat time
- Operating locks
- Continuous on, Continuous off
Can be set in the operating mode "Venetian blind/Rolling shutter" with eNet server:
- Change-over time for direction change
- Running direction invertible
- Operating locks
- Position for sun protection, twilight, lock-out protection and wind alarm
Supplementary functions with eNet server:
- Fully-encrypted radio transmission (AES-CCM) from eNet Server software version 2.0
- Update of the device software
- Reading of error memory
Technical Details
Specification
Rated voltage: AC 230 V ~, 50/60 Hz
Ambient temperature: _5 ... +45 C
Switching voltage: AC 250 V ~
Minimum actuation time in operating mode
- Blind: 0.1 s
- Shutter: 0.3 s
Running time: 1 ... 600 s
Running time default setting: 120 s
Slat adjusting time: 0 ... 10 s
Switching current per output for AC 230 V ~
- Ohmic: 16 A (AC1)
- For switching current > 10 A connecting cable 2.5 mm_
- Fluorescent lamps: 4 AX
Switching current neighbouring load outputs: _ 20 A
Current carrying capacity of device: max. 80 A
Min. switching current AC: 100 mA
Contact type: µ
Stand-by power: max. 0.5 W
Connected load per output:
- Motors: 1000 W
- Incandescent lamps: 2300 W
- HV halogen lamps: 2000 W
- Electronic transformers: 1500 W
- Inductive transformers: 1000 VA
- HV LED lamps: typical 500 W
- Compact fluorescent lamps: typical 500 W
- Fluorescent lamps non-compensated: 920 VA
- Capacitive load: 690 VA (560 µF)
Connection, outputs
- Connection mode: screw terminals
- single wire: 1.5 ... 4 mm_
- stranded without ferrule: 0.75 ... 4 mm_
- stranded with ferrule: 0.5 ... 2.5 mm_
Mounting width: 72 mm (4 rail units)
Bus line
- Rated voltage: DC 12 V SELV
- Current consumption: 60 mA
- Connection bus: terminal
- Cable length: max. 3 m
Properties
Properties
Technology | Wireless Control |
Brand | JUNG |
Mounting | DIN Rail |
Mounting Width | 4MW |