INTESIS
INKNXUNI001I000
Universal IR Air Conditioner to KNX Interface
Product code:
INKNXUNI001I000
The Universal InfraRed (IR)-KNX gateway allows a complete and natural integration of any Air Conditioner unit (with an infrared receiver) into KNX systems.
The previous part number for this item was IS-IR-KNX-1i
Description
FEATURES
- KNX certified.
- Configured by ETS standard configuration tool.
- Offered all the required DPT objects to be compatible with all KNX thermostats in the market.
- Built-in room temperature sensor and 2 binary inputs.
- Auto-Learn function to automatically set the IR remote controller configuration.
- Energy efficiency functions, such as Òtimeout, Òopen window or ÒOccupancy. Costs related to HVAC systems in a building are one of the highest and these functions allow to reduce them.
- Simultaneous control of the AC unit by the IR remote controller and by KNX, thanks to IR receptor in device.
- Up to 5 scenes can be saved and executed from KNX.
INFRARED COMMUNICATION WITH THE INDOOR UNIT
- The gateway allows the control of the main AC functions via infrared commands. But also, thanks to the IR receiver that the device is equipped with, it is possible to know the real status of the AC unit even the user is controlling it by the manufacturer IR remote controller.
EASY TO SET UP BY ETS
- The connection between the two networks is quickly set up in the ETS configuration tool using the product database available to download. Moreover, the Auto-Learn function helps to reduce significantly the configuration time.
Technical Details
Specification
Enclosure: ABS (V-0). 2,1 mm thickness PC (V-2). 1 mm thickness
Dimensions: 81 x 78 x 28 mm
Weight: 76 g
Colour: Ivory white
Power supply: 29V DC, 17mA. Supplied through KNX bus
Mounting: Wall and desktop
LED indicators: 1 x Device status and KNX programming
Push buttons: 1 x KNX programming.
Binary inputs
- 2 x binary inputs for potential-free contacts.
- Signal cable length: 5m unshielded, may be extended up to 20m with twisted.
- Compliant with the following standards:
- IEC61000-4-2: level 4 - 15kV (air discharge) - 8kV (contact discharge) MIL STD 883E-Method 3015-7: class3B
Console port: Mini USB port for console usage
Configuration: Configuration with ETS
Operating Temperature: From 0oC to 40oC
Operating humidity: <93% HR, no condensation
Stock humidity: <93% HR, no condensation
Properties
Properties
Technology | KNX |
Brand | INTESIS |
Mounting | Surface |
Operating voltage | KNX Bus (29VDC) |
IP rating | IP20 |