HeatingBOX 230V 8X V2. Heating actuator for up to 8 outputs 230VAC and 8 inputs
ZENNIO ZCL-8H230V2

HeatingBOX 230V 8X V2. Heating actuator for up to 8 outputs 230VAC and 8 inputs

Product code: ZCL8H230V2
Actuator for climate systems based on water pipes which allows the control of up to 8 outputs for on/off valves operated at 230 VAC by means of triacs with short-circuit protection. It includes independent thermostat for each output, 8 analogue-digital inputs and a module with 10 logical functions. It has a sole power input for all the outputs, as well as a common neutral for an easier installation of the valves. It allows manual control of the outputs with status indication through LEDs.
Price (Excluding VAT)
£214.81

Description

  • 8 configurable outputs for 230 VAC valve control
  • 8 thermostats
  • 8 analog/digital inputs
  • 10 logic functions
  • Manual control through buttons and LED status indicators
  • Common 230 VAC input supply for all the outputs
  • Total data saving on KNX bus failure
  • Integrated KNX BCU (TP1-256)
  • Dimensions 67 x 90 x 70 mm (4 DIN units)
  • DIN rail mounting according to IEC 60715 TH35, with fixing clamp
  • Conformity with the CE, UKCA, RCM directives (marks on the right side). 


Zennio Thermostats:

Technical Details

Specification

KNX supply

Voltage (typical): 29 VDC SELV
Voltage range: 21-31 VDC
Maximum consumption Voltage:  
29 VDC (typical): 12.9mA, 374.1mW
24 VDC1: 17.5mA, 420mW
Connection type: Typical TP1 bus connector for 0.8 mm Ø rigid cable


External power supply: 230 V 50/60 Hz
Operation temperature: 0 .. +55 °C
Storage temperature: -20 .. +55 °C
Operation humidity: 5 .. 95%
Storage humidity: 5 .. 95%
Complementary characteristics: Class B
Protection class / Overvoltage category: II / III (4000 V)
Operation type: Continuous operation
Device action type: Type 1
Electrical stress period: Long
Degree of protection / Pollution degree: IP20 / 2 (clean environment)
Installation: Independent device to be mounted inside electrical panels with DIN rail (IEC 60715)
Minimum clearances: Not required
Response on KNX bus failure: Data saving according to parameterization
Response on KNX bus restart: Data recovery according to parameterization
Operation indicator: The programming LED indicates programming mode (red) and test mode (green). Each output LED indicates its status (fixed=active output; flashing=overload or short-circuit). The blue blinking of the programming LED indicates a 3 minutes lock due to the suffering of 4 short- circuits/overloads in less than 3 minutes.
Weight: 181 g
PCB CTI index: 175 V
Housing material / Ball pressure test temperature: PC FR V0 halogen free / 75 °C (housing) - 125 °C (connectors)

Properties

Properties

Brand ZENNIO
Technology KNX
Mounting DIN Rail
Inputs 8
Operating voltage KNX Bus (29VDC)
Outputs 8
HVAC support Regulation
IP rating IP20
Mounting Width 4MW

Documents & Downloads